What lightning data do you have for the site? The wizard prefers NSG from a lightning location system, then NG from a flash-density map — or looks it up on a satellite map.

→ N_SG = k · N_G = 8.0 /km²/yr will be used in the calculation (eq. A.1).

2 · Structure

Geometry and physical character. Like the real wizard, every option shows the coefficient it resolves to.

3 · Power lines

Each connected service section is a card — flashes to and near it add S3/S4 risk. The real wizard takes any number of sections per service.

Power line 1

4 · Telecom lines

The short overhead telecom line out-injects the long buried power line here — C_I and C_T at work.

Telecom line 1

5 · Risk zones

Risk is computed and judged per zone (Ed. 3:2024). Zone templates prefill typical values in the real wizard.

6 · Results — risk R per zone

R > R_T · protection required
ZoneRisk Rvs R_T = 10⁻⁵Verdict
Z1 — Entrance plaza2.1×10⁻¹⁰Pass
Z2 — Offices3.8×10⁻⁵×3.8Exceeds
Z3 — Archive (governing)3.6×10⁻⁴×36Exceeds

Component breakdown — governing zone (R = R_L1 + R_L2)

Recommended: Class I LPS + SPDs LPL I at both line entrances → governing zone 5.5×10⁻⁶ ✓ — every zone below R_T. The full report prints the post-measure factor tables so the projection is checkable.
Run this on your structure — free

Figures are the validated engine's output for this sample building (IEC 62305-2 Ed. 3:2024) — shown here as a fixed walkthrough. Your structure gets its own live computation, with every step clause-referenced.

Want this on your real structures?

The wizard and on-screen verdict are free — create an account and assess your first structure now. The full clause-referenced report is a one-off purchase.